| description: | ZQAM1 Single-phase meter is used to measure electric power in single-phase 50Hz or 60Hz AC circuit. It should be fixed to use with the limited working temperature of -30℃~+55℃ and the relative humidity of not exceeding 95%, and without the corrosive gas and salty spray in the air.
The dimension is specially designed for export, suitable for the tropical rainforest climate.
Structure
1. Case: one-piece steel base, transparent glass cover, extended steel terminal cover;
2. Bearing: magnetic bearing or single jewel bearing
3. Register: wheel type, five or six digitals;
4. Frame: molded aluminum alloy;
5. Braking component: Al. Ni. Co single pole magnet;
6. Driving component:voltage steel core is complete rivet pressing type,adjusting screw type light load adjustment, slide resistance type phase adjustment;
Main technical data
|
Reference voltage |
110V, 120V, 220V, 230V, 240V |
|
Frequency |
50Hz or 60Hz |
|
Basic current (rated max, current) |
1.5(6)A, 5(20)A, 10(40)A, 15(60)A, 20(80)A, 30(100)A |
|
Class |
2 |
|
Voltage circuit consumption |
1.2W 6VA |
|
Current circuit consumption |
2.5VA |
|
Basic speed |
18 r/min |
|
Torque |
4.0×10-4N·M |
|
Weight of rotor |
19g |
|
Weight of meter |
1.7kg |
|
Standard |
IEC62053-11, GB/T15283-94 | |